Fire Detection & Alarm System

A Heat & smoke detector is a device that senses heat & smoke, typically as an indicator of fire. Commercial Heat & smoke detectors issue a signal to a fire alarm control panel as part of a fire alarm system, while household heat & smoke detectors, also known as Heat & smoke alarms, generally issue an audible or visual alarm from the detector itself or several detectors if there are multiple heat & smoke detectors interlinked.

UL/FM Fire Alarm Control Panel

LPCB Certified Fire Alarm
Control Panel

UL/FM FIRE ALARM CONTROL PANE

Red Analog FACP 2-LOOP AS0820-10

Specifications

  • Construction: 16AWG sheet steel
  • Dimensions: 14.5”W x 18.9”H x 4.25” D
  • Weight (without batteries): 20lb
  • Mains voltage supply: 115 or 230V AC 50 or 60 Hz.(specify when ordering, default is 115V)
  • Mains supply fuse: 1.6A 250V
  • Maintenance-Free sealed batteries
  • Aux 24V supply: Fused at 500 milliamps
  • Battery (24 hour standby): 9Ah 12V (2 per panel) (non-networked)
  • Fault contact rating: 30V DC 1 Amp
  • Fire contact rating: 30V DC 1 Amp
  • Alarm contact rating: 30V DC 1 Amp
  • NAC output rating: 3.1V across both channels, 2.3V across any one
  • Detection loop: 250 milliamp output
  • Serial expansion port: Serial RS485
  • PC port: Serial RS232
  • Network connection: Optional network Cards allow the use of e-Net networking or VESnet networking
  • NAC Synchronization: Internal Support
  • NAC Protocols: System Sensor, Wheelock, Gentex, Amseco

Elite [H] 4 Loop Panel, Red AS1440-10

Specifications

  • Primary AC: 120VAC @ 2 Amps 60hz (Optional 240 VAC 50hz)
  • Output DC: 24VDC @ 4 Amps
  • Power Supply: 5.25 Amp regulated and integrated
  • Charger Current: 1.25 Amps max.
  • Dimensions: 14.5” W x 24”H x 5” D
  • Weight: 25 lbs. (without batteries)
  • Color: Red (optional gray)
  • Display: 8-line x 40-character LCD (320 characters’ total)
  • Zones: 500 Zones per network
  • SLC loops: 2 or 4 (class A or B)
  • Devices per loop: 126 sensors & modules (800 addresses + sub-addresses max. per panel)
  • NAC Outputs: (4) 1.6 Amp @ 24VDC (class B)
  • Relay Outputs: (5) Form C 1 Amp @ 30VDC
  • Voltage Outputs: (3) 500mA @ 24VDC, reverse polarity supervised
  • Power: 500mA @ 24VDC
  • Inputs: (3) digital pull downs

Addressable Multi Heat Detector ROR & FT AS2010-00

Specifications

  • Operating Voltage: 17-41 VDC
  • Standby Current: 350μA
  • Alarm Current: 500μA
  • Transmission Method: DCP—Digital Communication Protocol
  • Maximum Humidity: 95% RH Non-Condensing
  • UL Temperature Range: 135º F to 190º F
  • Operating Temperature Range: 32º F to 190º F
  • Rate of Rise: 15º F/ Min
  • Color & Case Material: Bone/ White – ABS Blend
  • Weight: 3.2 oz., (4.9 oz. with 4” base)

Addressable Photoelectric Smoke Detector AS2011-00

Specifications

  • Operating Voltage: 17-41 VDC
  • Standby Current: 450μA
  • Alarm Current: 540μA
  • Transmission Method: DCP—Digital Communication Protocol
  • Maximum Humidity: 95% RH Non-Condensing
  • UL Temperature Range: 32º F to 115º F
  • Operating Temperature Range: 14º F to 122º F
  • Sensitivity Range:7 – 4.0%/ FT @ 300 FPM, 7 – 3.86%/ FT @ 2000 FPM, 7 – 2.65%/ FT @ 4000 FPM
  • Air Velocity Range: 0-4000 fpm
  • Color & Case Material: Bone/ White – ABS Blend
  • Weight: 3.4 oz., (5.1 oz. with 4” base)

Addressable Detector Base AS7001-00

Specifications

  • The Dealer shall furnish and install where indicated on the plans, models AS2011 Photoelectric Smoke Sensor, AS2010 Heat Sensor and AS2012 Multi-Criteria Sensors. The selected sensor shall be attached to the AS7001 and permit direct interchange between the listed sensors. The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be optional and can be implemented when required.
  • Note: SLC maximum resistance is 50 ohms.

LPCB Certified Fire Alarm Control Panel

LPCB Fire Alarm Control
Panel

Specifications

 

  • Certified EN54-2:1997 +A1:2006, EN54- 4:1997 + A1:2002 + A2:2006
  • LPCB Approved
  • Using advance microprocessor technology with Large memory capacity
  • Enhance user interface combining LCD Touch screen and keypad access
  • Support real time visual algorithm
  • Enhance false alarm prevention

CP Conventional Panel 8 Zones - Red - 230 VAC AS1848-11

Specifications

CP Conventional Panel 4 Zones - Red - 230 VAC AS1844-11

Specifications

AW-AFP2189 Addressable Fire Alarm Control Panel

Specifications

  • Mains power supply: AC 220V±20%/50Hz or DC24V
  • Backup power supply: DC24V maintenance-free battery BAT12V/5AH
  • System Operating Environment
  • Ambient temperature: -10℃~+55℃
  • Ambient humidity: ≤95% (40℃±2℃, no condensation)

AW-AFP2100 Addressable Fire Alarm Control Panel

Specifications

  • Each loop card has 2 loops, with 324 addresses as alarm/control points of each loop, the capacity of each loop card is 324*2=648(addresses)
  • Each wall mounted AW-AFP2100 panel can be installed maximum 3 loop cards, the maxium capacity is 648*3=1944(addresses). Over 1944 addresses, use the cabinet panel, the cabinet panel can be installed maxium 40 loop cards, the maximum capacity is 648*40=25920(addresses)
  • Peer-to-peer with max.20 AW-AFP2100 panels, the maxium system capacity: 25920*20=518400(addresses)
  • Maximum simultaneous alarm of each host:
  • Fire alarm: 500
  • Trouble: 500
  • Feedback: 500

AW-CSD501-4W 4 Wire Conventional Smoke Detector

  • Two LEDs on each detector provide local 360° visible alarm indication. They flash every six seconds indicating that power is applied and the detector is working properly. The LEDs latch on in alarm. LEDs will be off when a trouble condition exists indicating that the detector sensitivity is outside the listed limit. The alarm can be reset only by a momentary power interruption.
  • The detector that initiated the alarm condition will have its red LED and relays latched until reset by panel.
  • Heat detector and smoke & heat detector combine a photo electronic sensing chamber and a temperature heat detector.

Specifications

Conventional Photo Electric Smoke - H AS2032-00

Specifications

  • Low Profile一1.8″ high (with base)
  • 2 wire base compatibility, relay bases available
  • Highly stable operation, RF/Transient protection
  • Low standby current, 45NA at 24VDC
  • Two built-in power/alarm LEDs
  • Non-directional smoke chamber
  • Vandal resistant security locking feature
  • Removable smoke labyrinth for cleaning or replacement

Conventional Heat Sensor 135° F (H) AS2020-00

Specifications

  • Low Profile一1.8″ high (with base)
  • 2 wire base compatibility, relay bases available
  • Highly stable operation, RF/Transient protection
  • Low standby current, 45NA at 24VDC
  • Two built-in power/alarm LEDs
  • Non-directional smoke chamber
  • Vandal resistant security locking feature
  • Removable smoke labyrinth for cleaning or replacement